7ML19985LY01 SITRANS LR560 (FF) – INSTRUCTION MANUAL Page 51
mmmmm
AMS Device Manager
Level Transducer Block Parameters
Operation (LTB)
Navigate to Configure/Setup > LTB > Operation and click Simulation to open the dialog
window for access to:
Simulation (Input)
Allows you to simulate the sensor value which is input to the Level Transducer Block. This
tests everything between the Level Transducer Block and Output.
Simulation
Simulation Value
1) Set Simulation to Fixed value or Ramp, and click Apply.
2) If you select Fixed value, enter a Simulation Value and click Apply.
3) Or select Ramp, enter the RAMP start, end, number of steps, and step length,
and click Apply.
4) After simulation is complete, set Simulation to OFF and click Apply.
Notes:
To activate simulation via AMS Device Manager or the 375 Field Communicator,
simulation must also be set to Enabled on the device. See Simulate Enable (4.12.) on
page 120.
Before enabling or disabling Simulation, put LTB Block into OOS mode (see
Changing Block Modes
on page 49).
After changes have been made, LTB must be returned to AUTO mode.
Ramp start Range: –999999 to 999999. Default: 0 m
Ramp end Range: –999999 to 999999. Default: 0 m
Number of steps Range: 1 to 65535. Default: 10
Step length Range: 1 to 65535. Default: 5 s