Page 92 SITRANS LR560 (FF) – INSTRUCTION MANUAL 7ML19985LY01
mmmmm
Parameters
2.3.5.4. Low Level Point
The level when the material is at Low Calibration Point. The unit is defined
in Level Unit (2.3.2.).
2.3.5.5. High Level Point
The level when the material is at High Calibration Point. The unit is defined
in Level Unit (2.3.2.).
2.3.5.6. Level Offset
A constant offset that can be added to Level. The unit is defined in Level
Unit (2.3.2.).
2.3.6. Rate
2.3.6.1. Response Rate
Sets the reaction speed of the device to measurement changes.
Use a setting just faster than the maximum filling or emptying rate
(whichever is faster).
Values
Range: -999999 to 999999
Default: 0%
Values
Range: -999999 to 999999
Default: 100%
Values
Range: -999999 to 999999
Default: 0%
Notes:
Changing Response Rate resets Fill Rate/Min (2.3.6.2.), and Empty
rate/Min (2.3.6.3.).
Selecting SLOW Response Rate changes setting for
Average amount
(2.8.3.)
to 0.9.
Response Rate
(2.3.6.1.)
Fill Rate/Min (2.3.6.2.)/
Empty rate/Min (2.3.6.3.)
slow 0.1 m/min (0.32 ft/min)
* medium
1.0 m/min (3.28 ft/min)
fast
10.0 m/min (32.8 ft/min)