● Gray: Complete building
● Blue: Façade or part of a facade
● Green: Rooms of a renter, e.g., one floor
● Orange, red: Local, manual operation
The functions are grouped into local and central functions depending on
whether the function acts on one or multiple blinds in a room, or on an entire
group of blinds, e.g., on all blinds of a facade.
Grouping by local and central functions for the examples from
the figure above
Local manual operation Automatic shading Wind speed monitoring Scheduler program
Central function n/a Determination of optimal
shading position in
dependence of sun
position
Measuring of wind speed
Monitoring of wind speed
Commanding of wind
protection position
Commanding of a
position in dependence of
daytime
Local function Commanding of manual
position
Positioning of blinds
Decision on which
position is commanded
automatically
Positioning of blinds
Positioning of blinds Positioning of blinds
The control concept is based on the following:
● Grouping into autonomous functions determining a set position for the
blinds
● Priority assignment to individual functions
● Evaluation of all functions and decision in favor of specific blinds position
based on priorities
Overview of autonomous functions to control blinds
Priorities depend on plant requirements. The table shows the typical priorities
in ascending format.
Function Description
Automatic shading Automatic determination of optimum blinds position based on current room use, solar
radiation, outdoor brightness, solar position, and HVAC status. In simple terms, this
function prevents glare in occupied rooms and uses solar energy for heating in
unoccupied rooms, or protects the building against undesired heat-up.
Manual operation (room, central) Manual operation allows users to themselves determine the blinds position via
buttons. If manual operation overrides a lower-priority function, a scheduler program
or local presence information will reactivate the function.
Presence-based influence
(room)
Locking of automatic operation upon entering a room, and activation of automatic
operation upon leaving a room. The presence-based function generally acts on the
same priority as manual operation.
Scheduler program A scheduler program opens, closes blinds at specific times, or commands them to a
specific shading position. Furthermore, automatic operation can be activated or
deactivated via scheduler program. Another priority may need to be commanded
depending on purpose. If, e.g., automatic operation should be activated at noon,
manual operation must be overridden by allowing the scheduler program to act on the
priority for manual operation. If the blinds are to be closed at night without allowing for
manual operation, a higher priority must be commanded.
Automatic shading at high priority For example, to prevent overheating it may be necessary to use automatic shading at
higher priority, which limits or prevents manual operation in certain situations.
Manual operation at high priority
(room, central)
Manual operation at high priority allows for positioning blinds and overriding low-
priority functions. For example, local operation can be overridden during, e.g., a
presentation. Or it can be ensured that neither automatic shading nor a scheduler will
drive the blinds up or down at an undesired time.