User Manual

Control concept
Desigo room automation
5
108 | 353 CM110664en_07
Function Description
Product protection, local Risks impacting a blind only, e.g., protection against collision with a service door
opening outward, are included in local product protection.
Product protection, central Environmental influences impacting a group of blinds are included in the central
functions for product protection. A common function in this category is protection of
blinds against damage from strong winds.
Maintenance position, central For maintenance or cleaning, blinds are commanded or blocked to a specific position
at high priority enabling staff to carry out all required work without risking injury due to
moving blinds.
Protection, central Blinds can be moved/driven up to provide escape or access routes for emergency
personnel in the event of a fire.
A very simple control contains just one or two functions; a complex plant may
use many or all available functions. In addition, the response of individual
functions may require parameterization depending on the requirements. The
following figure shows an example of a plant including all functions.
Lighting control
Suitable lighting products and intelligent control allow for optimum satisfaction
of various requirements.
Lighting products and their control are the primary means to create optimum
lighting conditions for building users:
Optimum workspace conditions (bright or darkened rooms)
Optimum lecturing/teaching conditions (presentation)
Comfort in living spaces
Mood lighting in entertainment spaces (restaurants, bars, etc.)
Other requirements may be:
Selection of priority
Determining shading position by solar
position
Selection of right automatic
position
Manual operation (button)
Selection of right automatic
position for high priority
Manual operation at high priority
(button)
Manual operation at high priority (btton,
management station)
Scheduler program
Product protection local (avoiding
collisions)
Product protection central
(wind, rain, frost)
Maintenance position
(blinds maintenance, window cleaning)
Central safety (fire alarm)
Scheduler program, high priority
Execute
resulting drive
command
Manual operation
(button, management station)
Presence-induced activation/
deactivation of automatic mode
Central function Local function
Products and