allowed to expire, that is, DPMon.RefVal is held at 1 during the transient
state. Only after expiry of the ramp up time does DPMon.RefVal revert to 0.
7. The ventilation system is already running (from step 6 on), that is, the fan
blades start rotating, the pressure builds up and the differential pressure
monitor detects delta p = X again, that is, DPMon.PrVal → 1. The alarm
monitoring function is active again. After expiry of the time [TiMonDvn], this
determines that there is no alarm condition present, because
[DPMon.PrVal(0) <> DPMon.RefVal (1)]. The system then operates 100%
correctly as described under step 1 above.
To simplify the time chart shown above, the connection to DPMon.EnAlm has
not been included.
9.3 Effects of BACnet properties on alarm
response
BACnet properties in function blocks
I = Input
O = Output
V = Value