Effects of BACnet properties on alarm response
9
140 | 353 CM110664en_07
and Close. The first end switch, the Open switch delivers the signals Fully open
or Not fully open. The second end switch, the Closed switch delivers the signals
Fully closed or Not fully closed. The following is an example of how to connect
the BO (binary output for commanding and integrating the Open switch) and BI
(the binary output for the closed switch):
Given the feedback signal [FbVal] Fully open, the Open and Close commands
follow the time sequence shown below, making use of all three deviation
monitoring times [TiMonDvn].
Since the BO block can handle the feedback of two different addresses, the
fire-protection damper solution can be further simplified by direct connection of
the Closed switch (Addr. 1) and Open switch (Addr. 2). In cases where both end
switches are simultaneously On or simultaneously Off, the BO block treats the
[FbVal] as invalid. Throughout this period, therefore, the alarm monitoring
function will return the value Alarm = OFFNORMAL. The circuit and time
sequence for normal and error conditions are as follows:
Circuit and time sequence for normal and error conditions: