Combination of multiple alarm suppressions
The above options to suppress alarms can overlap. For an object impacted
already by multiple types of suppression, the following rule applies: One type of
alarm suppression cannot be overridden by another type of alarm suppression.
AS_STA.
SupEvt
CMN_ALM.
SupEvt
CMN_ALM.
EnSupEcp
FB.SupEcpt FB.EnEvt Resulting alarm suppression
for function block
True • • • • suppressed
• • • • (F, F, F) suppressed
False False • • (T,T,T) not suppressed
False True False • (T,T,T) suppressed
False True True True (T,T,T) not suppressed
False True True False (T,T,T) suppressed
9.11 Alarm message texts
Desigo contains all the alarm texts necessary to help the user maintain an
overview and an understanding of the alarms. These alarm texts can be freely
defined in the engineering tool for each alarm source individually. If this is not
done, text will be generated automatically on the basis of the Technical
Designation of the individual function blocks. In a third category are the
predefined alarm texts used in conjunction with device faults.
The Desigo system supports alarm message texts.
For Desigo PX the message texts for TO_OFFNORMAL, TO_FAULT and
TO_NORMAL alarms are entered as an Array [3] in the BACnet property
[Message_Text]. For Desigo room automation the BACnet Property
Event_Message_Texts_Config is used.
For Desigo PX if no alarm message text has been entered for an alarm source,
or if the alarm message text for a given state (e.g., TO_FAULT) has been left
blank, an alarm message text will be generated from the existing descriptions.
Longer messages are divided into segments with forward slashes // so that the
client can display the message over several lines. Each segment may contain a
maximum of 70 characters, with a maximum of three segments separated by //
for any one message.
System alarms and events of the BACnet Device Info Object use text messages
which cannot be configured, e.g., Battery low.
System alarms and events of the BACnet Device Info Object use non-
configured text messages whose contents are language-dependent. These
Project-spec
.
Description
Standard
Description
Configured alarm
message texts
Non-configured
message texts