Operating states
No power supply
STOP
I/O scan active
Ready for wiring test (only possible without D-MAP program loaded)
(PXM20, for PTM modules only)
D-MAP program processing stopped
Communication with XWP: Master reset, complete loading and delta loading
allowed
BACnet communication with Desigo CC and PXM20: ReadProperty,
WriteProperty, Who-Has, COVs, EventNotification, AcknowledgeAlarm
GetEventInformation
COVs: For values changed by the operator, values cannot be changed by the
program
Alarming: Alarm monitoring inactive, no new alarms or events are generated
(the device info object can still generate alarms and system events).
Notification of saved alarms and events is possible if recipient lists are set
up. GetEventInformation and AcknowledgeAlarm possible.
Primary server in the STOP state: Primary server is not active, that is, no life
check, no time synchronization and no replication of global objects
Backup server in the STOP state: The backup server is not active, that is, no
time synchronization and no replication of global objects by primary server.
The backup server will not accept changes to global objects by a client.
I/O scan active
Wiring test not allowed
D-MAP program processing active
Communication with XWP: Master reset and complete loading not allowed,
delta loading allowed
BACnet communication with Desigo CC and PXM20: ReadProperty,
WriteProperty, Who-Has, COVs, EventNotification, AcknowledgeAlarm
GetEventInformation.
COVs: For values changed by the program and operator
Alarming: Alarm monitoring active, notification of alarms and events,
GetEventInformation and AcknowledgeAlarm
STOP
Mains OFF
BACnet: Download
required
COMA
RUN
BACnet: Operational
BACnet: Operational
15: Delta loading
16: Delta loading
7: Restart 9: Reset
4: RUN Cmd
5: STOP Cmd
7: Restart 9: Reset
14: Load
13: Master reset
10: Fatal Error
12: Reanimation
11: Fatal Error
1: Power failure 2: Power restored STOP
1: Power failure
2: Power restored RUN
1: Power failure
2: Power restored COMA
Mains off
RUN