User Manual

Automation stations
Data storage
18
234 | 353 CM110664en_07
3. The D-MAP program code is read from the flash memory (3a). The program
data is modified in the RAM (3b). Non-volatile process variables (e.g., adaptive
control parameters, hours run, etc.) are written by the function blocks into the
flash memory (3c) at regular intervals (once per day) or saved in the battery
supported RAM.
4. At each restart of the automation station, a copy of the data (data blocks) is
created in the RAM (4) from the flash memory (including all communication and
D-MAP changes).
Processing the D-MAP
program
Starting the automation
station