User Manual

Logical I/O blocks
Addressing the I/O blocks
19
CM110664en_07 269 | 353
Configuration Profile
1 2 3 4 5 6
Enable operating mode
StandBy ON ON ON ON ON ON
Auto ON ON ON ON ON ON
Fan1 ON ON ON ON ON ON
Fan2 OFF OFF ON ON ON ON
Fan3 OFF OFF OFF OFF ON ON
KonfLCD
Symbol Standby ON ON ON ON ON ON
Symbol Auto ON ON ON ON ON ON
Symbol Fan1 ON ON ON ON ON ON
Symbol Fan2 OFF OFF ON ON ON ON
Symbol Fan3 OFF OFF OFF OFF ON ON
TempUnit °C °F °C °F °C °F
This profile (or configuration number) is always valid for one room unit only. It
is used to configure the objects ConfigLCD and EnableOperatingMode and to
define how the room unit is to operate (e.g., °C or °F).
In principle, the profile can be attached to any other object.
This configuration applies only to the QAX33.1 and QAX34.1 room units.
Configuration of the object ConfigLCD is only relevant in the case of the
QAX34.1, as this is the only unit with a display in °C or °F.
The configuration of the object EnableOperatingMode is only relevant in the
case of the QAX33.1 or QAX34.1, as only these two room units have the option
of selecting Fan1, Fan2 or Fan3.
Where QAX units without an address switch are still in use, only one room unit
per automation station can be integrated. The room unit number in such cases
is then "1".
LonWorks addressing
There are two ways to integrate data points from LonWorks devices:
via Discipline I/O
via standard inputs/outputs (the latter approach is only sensible with a
small number of data points to be integrated, e.g., from third-party devices)
The block registers the control variables and output variables of the RX devices
(outside the CFC chart) in accordance with the information in the [IOAddr]
property (Input/output address).
Addressing starts with the prefix "L=".
L=DeviceType DeviceNo. GroupIndex(MappingTableNo.)
DeviceType: M (Master), S (Slave)
DeviceNo: Field device identification number
GroupIndex: Group identification: Up to 4 similar groups of an application
unit may exist in the field device (e.g., lighting or window-blind groups). The
group index number is optional.
MappingTableNo: Number of the mapping table which is valid for that
Discipline I/O.
More than one device can be specified for each [IOAddr] string. The devices are
separated with a semicolon. However, the maximum [IOAddr] string length of
60 characters must not be exceeded.
Address syntax
Addressing via