Logical I/O blocks
Slope [Slpe] and Intercept [Icpt]
19
272 | 353 CM110664en_07
Value (decimal) Text
92 Reference object cannot be commanded.
93 Actual operating mode not found in command list.
94 Invalid priority set for command (valid : 2,4,14,16).
95 Invalid object number configured in sequence table.
96 Invalid object type configured in sequence table.
97 Invalid step control configured in sequence table.
98 Neighboring object not reachable.
99 Command lists indicate different variables.
100 Invalid calendar reference.
101 Configured switch kind not supported by destination controller.
102 Multistate mapping error.
19.9 Slope [Slpe] and Intercept [Icpt]
[Slpe] and [Icpt] value exist for:
I/O modules (PX Modular and PX Compact)
These values impact signal type (the I/O module).
Siemens field devices
These values affect the combination of Slpe and Icpt values for the signal
type, the field device and its measurement and positioning range. XWP
automatically enters these values, and they can be changed there, e.g., to
consider the line resistance of a sensor or to describe a third-party sensor.
BACnet referencing
PPS2 interface
The combined values [Slpe] and [Icpt] can be calculated as follows from
individual values for signal type (I/O module) and characteristic curve (field
device):