User Manual
Logical I/O blocks
Slope [Slpe] and Intercept [Icpt]
19
CM110664en_07 273 | 353
Siemens Building Technologies field devices: XWP automatically enters the
combined values [Slpe] and [Icpt] (for the signal type, the field device and its
measurement or positioning range) on the I/O block.
Third-party field devices: You can calculate the value [Slpe] and [Icpt] using
the Intercept Calculator.
[Slpe] and [Icpt] Analog Input
In the Desigo PX modular automation stations, the analog input block is used
with the following TX-I/O and PT-I/O modules:
Signal type
measurement
Description Standard
measuring range
Resolution on the
bus
Value range on
the bus
[Slpe] [Icpt]
R1K LG-Ni 1000 -50 … 150 °C 1/100 °C -5000 ... 15000 0.01 0
P100 Pt100 0 … 250 Ohm 1/100 Ohm 0 ... 25000 0.01 0
R250 Resistance 0 … 250 Ohm 1/100 Ohm 0 ... 25000 0.01 0
Pt100_4 Pt100 -50 ... 600 °C 1/100 °C -5000 ... 40000 0.01 0
P1K Pt1000 0 … 2 500 Ohm 1/10 Ohm 0 ... 25000 0.1 0
R2K5 Resistance 0 … 2 500 Ohm 1/10 Ohm 0 ... 25000 0.1 0
T1 PTC sensor -50 ... 150 °C 1/100 °C -5000 ... 15000 0.01 0
Ni1K LG-Ni 1000 -50 ... 180 °C 1/100 °C -5000 ... 18000 0.01 0
Pt1K375 Pt1000 (NA) -50 ... 180 °C 1/100 °C -5000 ... 18000 0.01 0
Pt1K385 Pt1000 (EU) -50 ... 600°C 1/100 °C -5000 ... 60000 0.01 0
NTC10K NTC sensor -40 ... 115 °C 1/100 °C -5000 ... 11500 0.01 0
NTC100K NTC sensor -40 ... 125 °C 1/100 °C -5000 ... 12500 0.01 0
U10 DC 0 ... 10V 0 … 10 Volt 1/1000 V 0 ... . 10000 0.001 0
I420 DC 4 ... 20mA 4 … 20 mA 1/1000 mA 4000 ... 20000 0.001 0
TX- and PT-I/O
modules PX modular