User Manual
Logical I/O blocks
Slope [Slpe] and Intercept [Icpt]
19
CM110664en_07 275 | 353
Signal type positioning Description Standard measuring range [Slpe] [Icpt]
Y10S DC 0…10 V 0 … 10 V 1000 0
Transfer of an analog control command to a room unit connected via the PPS2
interface. Only Object 195 (= Room temperature display) can be used in the
analog output block. As the value is already available as a converted or
referenced value, no conversion is required, that is, [Slpe] must be defined as 1
and [Icpt] as 0.
Line resistance with [Icpt]
For analog inputs (measurement of temperatures or resistances), most signal
types are calibrated at a line resistance of 1 Ohm. The [Icpt] can be changed at
the AI block if the line resistance deviates strongly from 1 Ohm.
Measuring resistances (internal resolution = 1/10 Ohm):
Line resistance [Slpe] [Icpt]
P1K (Pt1000)
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.0259740
0.0259740
0.0259740
0.0259740
-
259.48051
9
-
259.74026
0
-
260.00000
0
-
260.25974
0
0
0
0
0
0.259740
0
-0.259740
-0.519481
R2K5
P1K (0...2500 Ohm)
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.1
0.1
0.1
0.1
1
0
-1
-2
0
0
0
0
1
0
-1
-2
R250
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
1
0
-1
-2
0
0
0
0
1
0
-1
-2
R250
P100 (0...250 Ohm)*
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
0
-1
-2
-3
0
0
0
0
0
-1
-2
-3
Key
PPS2 interface