User Manual
Logical I/O blocks
Slope [Slpe] and Intercept [Icpt]
19
276 | 353 CM110664en_07
*
PT-I/O modules P100 is a four-wire type Default line resistance = 0 Ohm
Line resistance not compensated
TX-I/O modules with
island bus integration
Pt100_4 is a four-wire type Default line resistance = 0 Ohm
Line resistance not compensated
R250 is a two-wire type Default line resistance = 1 Ohm
TX-I/O modules with
BIM integration
Pt100_4 is a four-wire type Default line resistance = 0 Ohm
Line resistance not compensated
R250 is a two-wire type, but
must be connected to four
terminals using bridges
Default line resistance = 0 Ohm
Measuring temperature (internal resolution = 1/100 °C):
Line resistance [Slpe] [Icpt]
Pt 1K 385 3.85 0.259740
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
0.259740
0
-0.259740
-0.519481
Pt 1K 375 3.75 0.266667
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
0.266667
0
-0.266667
-0.533333
Ni1K 5 0.2
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
0.2
0
-0.2
-0.4
T1 9.57
10.39
11.31
12.36
0.104450 -50...0
°C
0.096246 0...50
°C
0.088417
50...100 °C
0.080893
100...150 °C
0 Ohm
Default = 1 Ohm
2 Ohm
3 Ohm
0.01
0.01
0.01
0.01
0.096246
0
-0.096246
-0.192493
Pt100_4
Pt100 is a four-wire type, default line resistance = 0 Ohm
-> Line resistance is not compensated