User Manual
Logical I/O blocks
Addressing entries for PXC…-U, PTM and P-Bus
19
CM110664en_07 279 | 353
Module type Signal type Parameters Example
Y250T 1...13, 1...13 P=3.1 (Y250T,8)
P=3.1 (Y250T,8,10)
Y420
AO, AOS, AOSL, AOL
- P=34.1 (Y420)
P=36.1 (AOS)
Binary Input D20, D20S
D42, D250 (only PT-
I/O)
- P=25.2 (D20)
DI, DIS, DIL, DISL
- P=26.3 (DIS)
Counter Input C - P=38.1 (C)
Info LED Q_LED
PX KNX: D=1001
- C=8.1(Q_LED)
Binary Output Q250_P, Q250A_P 0, 1...600 P=12.1 (Q250_P)
Q250
QD, Q250B, (only PT-
I/O)
- P=1.1 (QD)
P=14.1 (Q250)
DO, DOS, DOL, DOSL
- P=15.2 (DOS)
Multistate Input
Multistate Output
D20
D42, D250 (only PT-
I/O)
Binary - Mapping P=1.1;1.2 (D20)
Updown - Mapping
1:n - Mapping
DI, DIS, DIL, DISL
Q250
Q250B, QD (only PT-
I/O)
Binary - Mapping
P=7.1 (DIS)
P=1.1;1.2;1.3 (Q250)
Updown - Mapping
1:n - Mapping
Q250_P3 0, 1...600 P=1.1 (Q250_P3,120)
Q-M3
QD-M2 (only PT-I/O)
- P=1.1 (Q-M2)
P=1.1 (QD-M2)
DO, DOS, DOL, DOSL
- P=26.3 (DIS)
Signal types shown in
italics
are used to map virtual modules for use with I/O
OPEN at module level. Signal types AIS, AOS, DIS and DOS deliver a 16 bit
value with status information, while signal types AISL, AOSL, DISL and DOSL
deliver a 32 bit value with status information. All other signal types deliver a
16/32 bit value without status information.
While all the module types listed may be connected to any P-bus addresses,
not all module types have 16 channels.
Parameter values for the analog output, binary output and multistate output
blocks:
Failsafe function (emergency control function) if the transfer of data over the
P-bus fails (for longer than 4 seconds) or in the event of a power failure. (an
operating voltage of AC 24 V must be available).
NO -> Module output signal goes to 0 V.
KEEP -> Module output signal remains at previous value.
0...30 -> Module output signal 0 = 0 V, 1 = 0.33 V, etc. , … 30 = 10 V.
1…13, 1…13 Runtime ranges for On/Off signals (the ranges do not need to be
the same for On/Off). Values 1…13 correspond to the following runtimes:
1 = 8.5 ...13 seconds
2 = 13 ... 18 seconds
3 = 18 ...25 seconds
4 = 25 ...35 seconds
Parameter values
Y10S
Y250T