User Manual

Logical I/O blocks
Addressing entries for PXC…-U, PTM and P-Bus
19
280 | 353 CM110664en_07
5 = 35 ... 48 seconds
6 = 48 ... 66 seconds
7 = 1.1 ... 1.6 minutes
8 = 1.6 ... 2.3 minutes
9 = 2.3 ... 3.2 minutes
10 = 3.2 ... 4.5 minutes
11 = 4.5 ... 6.3 minutes
12 = 6.3 ... 9.0 minutes
13 = 9.0 ... 11 minutes
The PTM1.2Y250T(-M) module can only implement one runtime. It therefore
uses the opening-command runtime for closing commands.
0, 1…600 -> Pulse times, where 0 = 0.5 seconds and then 1 = 1 second, 2 = 2
seconds etc. up to 600 (=600 seconds).
Pulse times for island bus applications:
Values in the I/O address editor: 0...255 (corresponds to 0...25.5 seconds)
Default = 5 (corresponds to 0.5 seconds).
Addressing entries PX Compact (PXC…)
The addressing procedure is almost identical for Desigo PX compact and for
Desigo PX modular. However, the valid address ranges and signal types are not
the same as those used for the addressing of individual P-bus I/O modules.
For PX compact, the on-board I/O modules at the [IOAddr] pin start with a "C"
(prefix: "C=").
Address syntax: C=Module.Channel (Signal type, parameter)
Example:C=2.1 (Y10S, NO)
The table below shows the available address ranges and signal types, which
vary according to the Desigo PX compact automation station (each with its own
integrated, fixed configuration of I/Os) type.
Desigo
PX
compact
PXC10-TL
1
PXC12
PXC12-T
PXC22
PXC22-T
PXC36
PXC36-T
PXC52 Signal
type
Module Channel Module Channel Module Channel Module Channel Module Channel
Uni-
versal
Inputs
(UI: for
AI, DI)
1 1…4 1 1…6
X1…X6
1 1…8
X1…X8
1 1…12
X1…X12
1 1…16
X1…X16
R1K,
U10, D20
T1, P1K,
N1K
Digital
Inputs
(DI)
(Counter
Input)
2 1…4 2 1…4
D1…D4
2 1…4
D1…D4
2 1…4
D1…D4
D20, C
Digital
Inputs
(DI)
3 1…4 3 1…8
D5…D12
3 1…12
D5…D16
D20
Analog
Outputs
(AO)
- - 4 1…4
Y1…Y2
4 1…4
Y1…Y4
4 1…6
Y1…Y6
4 1…8
Y1…Y8
Y10S
Digital
Outputs
(DO)
5 1…2 5 1…2
51…54
5 1…6
51…56
5 1…8
51…58
5 1…12
51…62
Q250
Q250_P, Q250A_P,
Q250_P3 ….