User Manual

Logical I/O blocks
Addressing entries for PXC…-U, PTM and P-Bus
19
CM110664en_07 281 | 353
Desigo
PX
compact
PXC10-TL
1
PXC12
PXC12-T
PXC22
PXC22-T
PXC36
PXC36-T
PXC52 Signal
type
Module Channel Module Channel Module Channel Module Channel Module Channel
Manual
switch
2
(only
PXC36-
S)
7 1…4 D_M3
LEDs 8 2…5 8 2…7 Q_LED
Info LED 8 1 8 1 8 1 8 1 8 1 Q_LED
PPS-2
signal
3
3
1..5
3
1..5
3
1..5
3
1..5
3
1..5 R1K,
U10, D20
PXC52
from
Desigo
V5
4
: Uni-
versal
Inputs /
Outputs
1
4
1…16
X1…X16
1…8
Y1…Y8
D20, C
R1K,
U10, D20
T1, P1K,
N1K,
Y10S
Key
1
For PXC10-TL the two Alarm1/2 buttons and the DIL switches1/2 are mapped to the
modules with the Address 3.
2
The manual switch can only be loaded into the application if the DIL switches (in the cover of
the PXC36-S) are set correctly.
3
Syntax for PPS-2 signal: Q=Romm device number.Object number (profile number). Up to five
devices can be connected.
4
The current UI and AO can all be configured as AI, DI, CI, or AO.
Signal type if no application is loaded (wiring test): X1...X16 = Y10S, Y1...Y8 =
R1K.
For Module 4, the universal outputs (UO for AO and DO) not only control
proportional actuators (AO), but can also be used as binary switch commands
(DO).
Analog Output = 0…10 V
Binary Output = DC 0 or 24 V, max. 22 mA with the use of an additional
external relay.
Layout of PXC52 housing with address ranges
X
1
0
X
1
1
X
1
2
D
1
D
2
D
3
D
4
D
5
D
6
D
7
D
8
X
1
3
X
1
4
X
1
5
D
9
X
1
6
C
P
-
C
P
+
AC24V
X1..16
MD001
D5..D16
MD003
51..62 = MD005
Y1..Y8 = MD004
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
G
N
D
26VA
D1..D4
MD002
Module 4