Application
Room air quality control
Rapid ventilation
Green leaf
Four light groups Manual switched control
Manual dimmed control
Automatic presence control
Automatic brightness control
Constant light control
Multi group constant light control
LED support on push buttons
Green Leaf - RoomOptiControl
Burn-in & operating hours function
Two blinds Manual control
Automatic control with anti glare function and energy
efficiency function
Green Leaf - RoomOptiControl
Collision detection
Loadable central functions
Application
Central
functions
4x Control room operating mode groups with:
Room mode and room setpoint distribution to rooms
Start optimization switches the heating on at the
appropriate time
Three delayed distribution groups of room operating
mode for big buildings
1x Seasonal compensation of room temperature
setpoints
2x Demand controlled hot water supply group
2x Demand controlled chilled water supply group with:
Condensation prevention shifts the base chilled
water setpoint to avoid condensation at chilled
ceiling radiant devices
Two pipe changeover control handles the heating /
cooling changeover for a two-pipe system
Free cooling manages the delivery of chilled water in
situations where this can be done with almost a zero
expenditure of energy, e.g., chiller plants with the
possibility to cool the water with the recoolers when
outside conditions are favorable.
1x Demand temperature control group with:
Relief function opens additional VAV without
demand to ensure stable working of the primary
plant
Changeover evaluation decide if the central air
should be used for heating or for cooling
Dew point evaluation is used to dehumidify at the
primary air handling unit to avoid condensation in
the rooms
Humidity demand evaluates room humidity to help
the pri
mary plant determine when to humidify or