User Manual
Desigo Open
Integration on management level
21
306 | 353 CM110664en_07
Desigo Open system Desigo Open application Data points
Desigo management platform Desigo CC
Energy monitoring, fire security,
access control and security
1,000 - 10,000
Desigo PX PX Open
Power distribution,
refrigeration machines
50 - 2,000
Desigo TX-I/0 TX Open
Pumps, variable speed drives,
meters, etc.
Max. 160
Desigo room automation / RX PXC3
Lighting and blinds
16 DALI groups
If a solution is not supported by HQ and RCs need a specific solution, HQ offers
Software Development Kits (SDKs) for experts. The regional companies can
develop their own solutions using Software Development Kits (SDKs).
The following SDKs are available:
● PX Open platform SDK
● TX Open platform SDK
21.1 Integration on management level
The integration of third-party devices and systems on the management level is
appropriate:
● For monitoring and operating plants that are not time-critical
● When process communication with other automation stations is not needed
Desigo CC
BACnet is a widely used communication protocol for building automation and
control networks. It defines a number of objects, services and data link layers. It
is an essential part of Desigo CC's openness for integrating any third-party
devices, using the BACnet/IP protocol. An online auto-discovery and
alternatively an offline EDE import are available for integrating third-party
devices.
See
BACnet 3rd party Integration Guide
(A6V10446271).
For more information about compliance and interoperability of Desigo products,
go to http://www.bacnetinternational.net/btl and search for Desigo.
A native Modbus-TCP driver lets you integrate a Modbus TCP server and
subsequent Modbus RTU devices via a protocol converter. An offline importer
supports the engineering workflow for integrating Modbus data points.
See
Modbus Integration Guide
(A6V10438039).
OLE for Process Control (OPC) is a communication standard for exchanging
data between windows based software applications and process control
hardware without any proprietary restrictions. It is a client/server technology,
where one application acts as the server providing data, and another acts as a
client using data. The most common specification
Data Access
(DA) defines a
set of objects, interfaces and method to facilitate the interoperability. OPC has
been extended to become a cross-platform communication standard, named
OPC Unified Architecture (OPC UA).
For more information about OPC, see the documentation by the OPC
Foundation (www.opcfoundation.org) and the OPC Training Institute
(www.opcti.com).
Which plant sections
can be integrated into
Desigo on which level?
SDKs
BACnet
BTL
Modbus-TCP
OPC