User Manual

System configuration
Devices
22
CM110664en_07 319 | 353
Key
1
PXM20, PX-Web and XWP are temporary alarm receivers.
2
Desigo CC is a configured alarm receiver. The number of entries in the notification class is
limited to 20. The total number of different configured alarm receivers across all notification
classes is limited to 30.
3
Max. number of BACnet references, COV servers: SubscribeCOV requests which can be
accepted. Example: 1400: 1 client and 1400 values or 2 clients and 700 values.
4
Max. number of BACnet references, COV client resources, i.e. values read from or written to
(commanded) your own automation station or a remote automation station.
BACnet client references are used in Input, Output, Scheduler, Trendlog and Group objects
(all NameRef_Type inputs with AddrKind = B). The configured alarm receivers of the
Notification Class objects do NOT require any BACnet client references.
The available number of BACnet client references shall address not more than 50 different
remote automation stations. If this value is exceeded the number of BACnet broadcast
messages on the network will increase.
Example: 400: 1 client and 400 values or 2 clients and 200 values.
5
Every active Trendlog object needs a BACnet reference.
Trends need 12 bytes per entry (irrespective of data type). Max. 64 KB can be allocated to
the log buffer (approx. 5,000 entries) for each Trendlog object. These log buffers are
assigned in D-MAP RAM. If the log buffer size is changed and there is insufficient D-MAP
RAM available, the Reliability property of the Trendlog object is set to Memory limit reached.
8
The address of the PPS-2 devices QAX84.1 and RXZ90.1 is always 1 (no address selection).
9
PX KNX = PXC001.D / PXC001-E.D and loaded PX KNX firmware.
10
PX Open = PXC001.D / PXC001-E.D with option module PXA40-RS1/RS2 and loaded PX
Open firmware.
14
Maximum 30 calendar entries.
15
The number of physical data points influences the reaction time of the application. If
minimum reaction times are specified, the number of physical data points may have to be
reduced.
The following relationship between reaction times and the number of physical data points
can be assumed:
- up to 150 physical data points = Reaction times < 1s
- up to 250 physical data points = Reaction times 1…2 s
- up to 350 physical data points = Reaction times 2…3 s
17
Number of switching times per day: 10; max. 5 BACnet references.
18
Number of switching times per day: 20; max. 5 BACnet references.
19
Every active trendlog multiple object needs a BACnet reference per logged value.
5 logged values are assumed for the number of trendlog multiple objects (number of
Trendlog / 5).
Trends need 12 bytes per entry (irrespective of data type).
Max. 64 KB can be allocated to the log buffer (approx. 5,000 entries) for each trendlog
object.
These log buffers are assigned in D-MAP RAM.
If the log buffer size is changed and there is insufficient D-MAP RAM available, the
Reliability property of the Trendlog object is set to Memory limit reached.
20
Dynamic objects are counted the same as non-dynamic objects for total limits.
* Limit* = Technical limit verified.
[ *] [Limit*] = Technical limit not verified.
[ ] [Limit] = Recommended limit not verified.
( ) (Limit) = Limit subject to proviso. Refer to footnotes.