User Manual

System configuration
Devices
22
CM110664en_07 325 | 353
22.4.11 Number of data points for DXR1
ASN Max. number of data points Description
DXR1.E04PDZ-
112
n/a 2 UI
DXR1.E09PDZ-
112
16 2 UI, 4 DO, 1 AO
DXR1.E09PDZ-
113
16 2 UI, 4 DO, 1 AO
DXR1.E10PL-112 22
a2
2 UI, 1 DI, 4 DO, 1 AO
DXR1.E10PL-113 19
b2
2 UI, 1 DI, 4 DO, 1 AO
DXR1.E02PLZ-
112
2 n/a
DXR1.M04PDZ-
112
n/a 2 UI
DXR1.M09PDZ-
112
16 2 UI, 4 DO, 1 AO
DXR1.M09PDZ-
113
16 2 UI, 4 DO, 1 AO
Key
a1
Total Number of PL-Link data points (under unconfigured status): 36
a2
Activate all selectable PL-Link devices, then check the maximum number of PL-Link data
points: 12
b1
Total Number of PL-Link data points (under unconfigured status): 28
b2
Activate all selectable PL-Link devices, then check the maximum number of PL-Link data
points: 9
22.4.12 Number of data points for DXR2
ASN Max. number of onboard IO- and KNX PL-Link data
points
Description
DXR2.x09 30 1 DI, 2 UI, 3 AO, 3 Relay
DXR2.x09T 30 1 DI, 2 UI, 4 Triac, 1 AO, 1 Relay
DXR2.x10 30 1 DI, 2 UI, 4 Triac, 3 Relay
DXR.x10PL 30 1 Pressure, 1 DI, 2 UI, 4 Triac, 1 AO
DXR.x10PLX 60 1 Pressure, 1 DI, 2 UI, 4 Triac, 1 AO
DXR2.x11 30 1 DI, 2 UI, 6 Triac, 2 AO
DXR2.x12P 30 1 Pressure, 1 DI, 2 UI, 6 Triac, 2 AO
DXR2.x12PX 60 1 Pressure, 1 DI, 2 UI, 6 Triac, 2 AO
DXR2.E17C-1 30 3 DI, 2 10K input impedance, 4 UI, 4 Triac, 4 AO
DXR2.E17CX-1 60 3 DI, 2 10K input impedance, 4 UI, 4 Triac, 4 AO
DXR2.x18 60 2 DI, 4 UI, 8 Triac, 4 AO