User Manual

Compatibility
Desigo system compatibility basics
23
CM110664en_07 335 | 353
Desigo CC
Desigo devices with a lower revision or the same revision as Desigo CC
Third-party BACnet devices with a higher revision than Desigo CC
Properties from earlier BACnet protocol revisions can be read by a BACnet device even if the
device supports a higher BACnet protocol revision than Desigo CC.
New properties from a BACnet protocol revision higher than Desigo CC cannot be read or
changed, because they are not recognized by Desigo CC.
The BACnet client ensures the backwards compatibility. Desigo CC should thus
have a BACnet revision that is at least the same as all of its connected BACnet
servers.
Usually, BACnet devices of a specific BACnet protocol revision fully support
earlier revision functions. However, since this is not true in all cases, we
recommend that you verify the compatibility in each case.
For an overview of the BACnet functions supported in Desigo, see
BACnet
Protocol Implementation Conformance Statement (PICS)
(CM110665).
Create and delete BACnet objects
The function can be used on Desigo PXC automation stations. Desigo room
automation stations PXC3 are not supported.
Third-party devices can be processed using the same functionality as long as
they support creating and deleting BACnet objects. PXM20 operating units do
not display dynamic objects.
Backup and restore BACnet devices
With the BACnet backup and restore function you can upload saved program
data (application program) from a BACnet device to Desigo CC and restore it to
the same or a new BACnet device.
The backup and restore function can only be run if the third-party BACnet
devices support it.
Compatibility Desigo Insight
For information on the system compatibility of the Desigo Insight management
station V6.0 SP2, see
Desigo Building Automation System 6.0 SP, Technical
Principles
(CM110664 / 2016-09-20).
Compatibility Desigo CC
For information on the system compatibility of the Desigo CC management
platform, see
Desigo CC System Description
(A6V10415500).
23.2.2 Compatibility with operating systems
Microsoft client operating systems
Tool Compatibility with Microsoft client operating systems
Windows 10 Professional / Enterprise
64-bit
XWP
ABT Site / ABT Pro
Yes*
Yes*
RXT10.5 Yes*
Desigo Configuration Module (DCM) Yes*
Status April 2020: