User Manual

Compatibility
Desigo system compatibility basics
23
CM110664en_07 339 | 353
23.2.13 Compatibility with Desigo PX / Desigo room
automation
The modular Desigo PX automation stations / system controllers
PXC00/50/100/200-E.D are supported as Desigo room automation system
function controllers for the PXC3 room automation stations. For performance
reasons, use PXC00-E.D where possible.
The local operator unit PXM10 cannot be used together with the following
devices:
PXC3 room automation stations
PX KNX (PXC001.D/PXC001-E.D)
PXG3.L/PXG3.M (BACnet router)
PXG3.Wxxx (web interface BACnet/IP of Desigo Control Point)
No I/O modules may be connected to the system controller LonWorks PXC00(-
E).D.
The modular series PXC…D (Desigo PX) and the PXC3 room automation
stations do not have a PPS2 connection.
23.2.14 Compatibility with Desigo RX tool
RXT10.5 supports only system integration via the PXX L11/L12 Controller.
You can only use LON standard tools NL220 (Newron System) or LonMaker
(Echelon) with project data from LonWorks PXC00(-E).D or PXC50/100/200 (-
E).D system controllers.
RXT10.x project data
All Desigo software and LibSets must be on the same PC and have the same
system version.
23.2.15 Compatibility with TX-I/O
TX-I/O modules
Product range TXM1.
8D
TXM1.
16D
TXM1.
8U
TXM1.
8U-
ML
TXM1.
8X
TXM1.
8X-
ML
TXM1.
6R
TXM1.
6R-M
TXM1.
8P
TXM1.
6RL
TXM1.
8RB
TXM1.
8T
Modular room automation
stations PXC3 (from index D)
- - - - -
Modular room automation
stations PXC..D
1
-
Key
1
Directly switched lighting applications (by the user) are not supported by the PXC..D
automation stations. For this reason, the configured button function of the digital input
modules is not available together with the PXC…D automation stations.
23.2.16 Compatibility with TX Open
The TXI1.OPEN, TXI2.OPEN, and TXI2-S.OPEN TX Open modules can only be
used together with the PXC50/100/200(-E).D and PXC22.1/PXC36.1(-E).D
automation stations.