23
340 | 353 CM110664en_07
23.3 Desigo Control Point
23.3.1 Compatibility with earlier systems
System compatibility PXM50-1
PXM40-1
PXM30-1
PXM50.E
PXM40.E
PXM30.E
PXG3.W100-1 PXG3.W200-1
Desigo PX primary plants
n.a. as of Desigo V4.0
Desigo room automation PXC3
n.a. as of Desigo V5.0
Desigo room automation DXR2
n.a. as of Desigo V6.0
BACnet third-party devices
n.a. as of BACnet revision 1.05 ( Desigo V4.0)
23.3.2 Compatibility with earlier devices
Desigo devices Desigo V6.0 Desigo Control Point
PXM50-1
PXM40-1
PXM30-1
PXM50.E
PXM40.E
PXM30.E
PXG3.W100-1 PXG3.W200-1
PXG3.W100
n.a. n.a.
PXM20-E
PXM30.E
PXM40
PXM40-1
PXM50
PXM50-1
PXM20-E
The dimensions for the cut out are the same as for mounting in the panel.
Supply voltage AC/DC 24 V.
Ethernet connection for communication.
No Power over Ethernet (PoE) connection on PXM30.E.
PX web
PX web graphics are not compatible with graphics for the new web
interface PXG3.Wx00-1.
No workflow is currently available to automate migration of PX web
graphics.
New graphics can be efficiently created, based on templates or existing
graphics.
PXM30.E
PXM20-E
PXA40-W0
PXA40-W1
PXA40-W2
PXG3.W100-1