23.4.2.1 Project case 1: Maintenance
Cases where you want to maintain your data and your site/project:
Edit an existing site/project. Edit an existing site/project without adding
automation stations or new features.
Extend the site with new devices of the same type, while keeping the same
old application version, and not using new features.
Replace a defect automation station with a new device of the same kind,
where the old application can be reused, e.g., replace a PX with a PX, a
PXC3 with a PXC3, a DXR2 with a DXR2.
The downgrade of automation station firmware is a potential security risk.
Doing so is strongly discouraged.
Benefit from the latest security releases. Upgrade the firmware of the
devices. Keep the applications as they are.
Prerequisites for upgrading from Desigo V6.2 Update (or
Update 2) to V6.2 Update 3 (Offline)
The XWP V6.2 Update 3 Tool and library and the ABT V4.0 Site/Pro Tool
and libraries are installed.
For details, see the release notes for the applicable tool: XWP, ABT Pro, and
ABT Site.
The needed RC local library V6.2 Update is installed.
For details, contact your local Tool Manager.
You have the project data and the credentials for the project you want to
work on.
The project data conversion from V6.2 to V6.2 Update happens
automatically.
When you open an XWP project, the XWP project is converted
automatically.
When you open an automation station in XWP, the CFC data is
converted automatically.
When you navigate to ABT Site, the conversion is done automatically.
Once XWP data and/or ABT data have been converted, you may not open the
project with an old tool version.
The new TIA15.1 version is included with the ABT V4.0 Tools installation.
Conversion is needed.
For details, see
Project Converter Wizard
(CM110633en28_06).
How to upgrade from Desigo V6.2 Update (or Update 2) to V6.2
Update 3 (Online)
1. Upgrade the automation stations firmware to the latest version or replace
the automation station with a new automation station.
Read back the parameters of the device with the tool, when the device
is available for readback.
Check the availability of the latest firmware per device in the VVS table.
For details about upgrading the automation station firmware, see the
documentation of the applicable tool: XWP, ABT Pro, and ABT Site.
2. Edit the application in the automation station.
For details, see the documentation of the applicable tool: XWP, ABT Pro,
and ABT Site.
3. You do not need to upgrade Desigo CC and/or Desigo Control Point.
23.4.2.2 Project case 2: Extension with new features
Cases where you want to use new features for one or several automation
stations: