User Manual
Compatibility of Desigo V6.2 Update 3 with PXC4 and PXC5
25
350 | 353 CM110664en_07
25 Compatibility of Desigo V6.2 Update 3
with PXC4 and PXC5
Overview
Online system Desigo V6.2 Update 3 with PXC4 and PXC5
● Full BACnet communication between the Desigo CC management platform
and the Desigo V6.2 Update 3 system.
● Full BACnet communication between the Desigo CC management platform
and the Desigo PXC4 and PXC5 system.
● BACnet communication between Desigo V6.2 Update 3 and Desigo PXC4
and PXC5: Via COV's.
For system limits of Desigo V6.2 Update 3, see Compatibility [➙ 333].
For system limits of Desigo PXC4 and PXC5, see
PXC4 & PXC5 Planning
Overview
(A6V11973797).
Prerequisites for extending Desigo V6.2 Update 3 (XWP
project) with PXC4 and PXC5
● Upgrade the management platform Desigo CC to V4.1.
● Make sure all PXC00...200..D primary controllers and room automation
products adhere to the Desigo V6.2 Update 3 compatibility.
● You are using Desigo Xworks Plus (XWP) V6.2.
● You are using ABT Site V4.0.
Engineering of Desigo V6.2 Update 3 projects with PXC4 and
PXC5
Network topology
Structure the network topology as follows: