User Manual

Control concept
Control concept and control blocks
5
66 | 353 CM110664en_07
Main functions and interfaces of I/O blocks
Function Inputs Description AI AVAL AO BI BVAL BO MI MVAL MO
Stop
transmission of
input signal
OoServ Out of service
Priority
mechanism
DefVal Default value
PrioArr Priority array
Local override Ovrr Override
OvrrVal Override value
Alarm value
monitoring
- Limits
- Reference
values
- Monitoring
periods
EnAlm Alarm enable
HiLm Upper limit
LoLm Lower limit
Nz Neutral zone
RefVal(s) Reference value
TiMonOn Monit. time
switch-on
TiMonOff Monit. time
switch-off
TiMonDvn Monit. time
deviation
Switching delays DlyOn Switch-on delay
DlyOff Switch-off delay
TbTiDly Time delay table
Switching action
Normal (motor)
Release
command
Trigger
Switch
Switch with
delay
SwiKind Switch kind
Function Outputs Description AI AVAL AO BI BVAL BO MI MVAL MO
Feedback
monitoring
PrVal Present value
FbVal Feedback value
Reliability
monitoring
Rlb Reliability
Fault monitoring Dstb Fault
Status
monitoring
TraSta Transitional
state
Priority
monitoring
SftyActv Safey priority
Active
CritActv Critical active
PgmActv Program active
PrPrio Present priority