The runtime of a damper or the coasting time for a multi-speed motor can be
defined in table [TbTiDly] to display or evaluate a transient state [TraSta]. The
time parameter can also influence the switching response depending on the
switch kind [SwiKind] used.
Plant fault
The block independently recognizes faults and reports them to the defined
alarm class [AlmCl], which for its part is responsible for distributing the alarms
to alarm receivers. Depending on the alarm function [AlmFnct] set in the block,
you may have to acknowledge the alarm and reset it after eliminating the alarm.
The faulted block on output [Dstb] is reset only after the user action is run. The
plant ramps up only after an alarm reset since both the local control, as a rule,
with this output is blocked for a fault and as superposed control triggered a
plant fault.
The alarm reset can be triggered:
● By triggering a common reset in the common alarm block CMN_ALM
● Via an alarm client
5.2 Local control design
Fault-related shutdown
The disturbance output [Dstb] for an I/O function block is activated when the
block recognizes a FAULT alarm (e.g., broken wire) or an OFFNORMAL alarm
(e.g., exceeding a limit value).
The following figure shows how a valve and a pump are forcibly shut down or
ramped up depending on the fault state.
Example forced set-up
A limit value [HiLm] is defined for the temperature in block AI Temp. As soon as
this threshold is reached, the output [Dstb] switches the valve via Enable
[EnSfty] for the analog output value to 100%. At the same time, the pump is
switched to off by Enable [EnSfty] for the Binary Output BO.
Example of fault-related shutdown
The block BI ThOvrld monitors the state of the pump’s thermal switch. If the
contact is triggered, the function block is activated based on the parameterized
reference value [RefVal] for [Dstb] output. The pump is shutdown through
Enable [EnSfty] of the Binary Output BO. The Binary Output BO further
monitors the contact’s feedback. In the event of a fault, where the feedback is
interrupted, e.g., the block reports the fault and shuts down itself via the back