Control concept
Closed-loop control strategy
5
88 | 353 CM110664en_07
Online diagnostics
A diagnostics screen for the PWR_CTL block is available online in Xworks Plus
(XWP).
The following states are displayed:
Present value: Operating state at the block output pin [PrVal]
Action: Transient state [TraSta] depending on actual switching conditions:
Up, down or hold
Present power: Value at the block output pin [PrPwr]
Status flag: In accordance with the BACnet definition, the value of [StaFlg]
is always Overridden. Alarms may also be displayed here.
Released aggregate or stage: This shows the current sequence entry, the
released object [RlsObj] and the released object stage
Last alarm/event message: Value at the block output pin [LstMsg]
5.4 Closed-loop control strategy
Controller types
For closed-loop control purposes, two controller blocks are provided in the
Desigo system, which cover the majority of requirements:
[PID_CTR]
[CAS_CTR]
The PID_CTR block is used as:
A universal stand-alone PID controller
A universal PID controller with external tracking
An individual sequence-controller element in a sequence controller or
sequence cascade controller
The PID_CTR block integrates the following functions:
Can be programmed for P, PI, PID or PD control action
Gain, integral action and derivative action can be programmed individually
Proportional control output with minimum and maximum limit control
Programmable gain factor
Programmable neutral zone
PID_CTR stand-alone
controller – Sequence
controller