User Manual

Control concept
Closed-loop control strategy
5
90 | 353 CM110664en_07
measured value [Xctl] is less than half of the [Nz], the output is driven for a
further 7 cycles, so that the measured value [Xctl] is as close as possible to the
middle of the [Nz]. The output signal [Yctr] then remains constant. The output
signal is only re-adjusted when the parameters move outside the [Nz] again.
If the PID_CTR block is configured as a P-controller or PD-controller, a
calibration point (Offset) [YctrOfs] can be specified, e.g., the P-controller can
be calibrated so that the set point is maintained with a 50% load.
With a 0% or 100% load, the P-deviation is then half the amplitude of the
proportional range [Gain].
[Track] is used, e.g., where the PI(D) controller, operates as a limit controller,
e.g., acting on a valve or actuator via an intermediary minimum or maximum
selector block. The tracking input ensures the availability of the controller
during the period in which it is blocked by the minimum or maximum selector
block. During this time, its integrator (and, hence, its output) is maintained at
the value of the signal received, so that if the limit conditions are violated, it is
able to respond immediately. [Track] is also used in conjunction with special
actuators with positioning feedback.
[Actg] is a characteristic parameter of the controller and indicates the
relationship between the setpoint deviation and the change in energy flow. A
distinction is made between direct action and indirect [Actg].
Direct control [Actg]: As the controlled variable rises, the controller output
increases, and as the controlled variable falls, so the controller output
decreases.
Example: Cooling or dehumidification – as the measured value rises above
the setpoint, so the flow of energy is required to increase.
Indirect control [Actg]: As the controlled variable decreases, the controller
output decreases.
Example: Heating or humidification – as the measured value falls below the
setpoint, so the flow of energy is required to increase.
Neutral zone [Nz]
P/PD controller
Tracking [Track]
Direct/reverse-acting
control action [Actg]