User Manual
Control concept
Desigo room automation
5
CM110664en_07 97 | 353
coordination of the individual technical installations must be optimized while
considering that the same type of installation may exist several times in one
room.
Room featuring:
1. HVAC zone (blue)
2. Lighting zones (yellow)
3. Shading/blinds zones (green)
The room typically is considered 1 HVAC zone influenced via a common
automation and control strategy regardless of number and type of installed
HVAC plant components (e.g., radiator, chilled ceiling, fan coil unit).
All lamps operated/automated together are grouped into a lighting zone
regardless of number and type of the installed lamps. A room typically has one
or several lighting zones.
All shading products (blinds) operated/automated together are grouped into a
shading zone regardless of number and type of the installed shading products.
A room typically has one or several shading zones.
Desigo room automation and room coordination
Specific functionality is set up for each zone of each technical installation: The
application functions. For Desigo room automation, this is supplemented by a
room-wide function coordination called room coordination.
Room coordination basically has two application functions:
1
3
2
2
3
HVAC zone
Lighting zone
Shading zone
Application function
structure