embedded device hosts inside the intranet via secure https communication and a
VPN.
1.1.9.3 Web Services with NORIS
NORIS stands for Northbound Open RESTful Integration Service. Desigo CC
allows external applications to read and write real time data as well as access
events or historical values, by using the provided REST (Representational State
Transfer) web service interfaces, e.g. NORIS. Web Services can be used for
applications such as Enterprise Software, Energy Management services, Facility
Management systems or Mobile Apps.
1.1.9.4 OPC Server
Desigo CC allows Enterprise applications or other management systems to access
real time values from integrated subsystems via OPC. The Desigo CC OPC Server
supports the OPC DA (Data Access) specification. In addition, an OPC UA wrapper
provides OPC UA Clients access to the exposed data.
1.1.9.5 BACnet Server
Desigo CC allows to 3rd party applications or other management systems to
access real time values from integrated subsystems via BACnet. The BACnet
Server complements the northbound interfaces of Desigo CC and it is used to
expose Desigo CC data, over a BACnet/IP network.
The BACnet Server acts as a gateway of non-BACnet network devices integrated
to Desigo CC, to be exposed over a BACnet IP network, as BACnet objects.
1.1.10 Certifications and Approval
Desigo CC has been tested against a wide range of domain- and country-specific
norms and standards, including:
● BACnet Revision 1.15, certified by BACnet Testing Laboratory as BACnet
Advanced Workstation Software (BTL B-AWS)
● AMEV recommendation BACnet 2011 compliant with Management Operation
Unit (MOU-B) profile
● IT security compliant with the ISA-99/IEC 62443 Security Level: SL1
● OPC DA V2.05a and V3.0 Server, certified by the OPC Foundation certification
program
● ISO500001 certification of Powermanager EM
● UL listed to UL864 10th edition Standard for Control Units and Accessories for
command and control when installed on a UL864 approved computer
● ULC listed to ULC-S527-11 3rd edition for command and control when installed
on a ULC-S527 approved computer
● UL listed to UL2572 for Mass Notification (for monitoring only when installed on
a UL2572 approved computer)
● ULC listed to ULC-S576 for Mass Notification (for monitoring only when
installed on a UL2572 approved computer)
● UL listed to UL-294 7th edition Standard for Safety - Access Control System
Units
● Support of pharmaceutical industry regulatory requirements, such as US FDA
21CFR Part 11, GMP Annex 11 or similar
Connecting Desigo CC functionality to FC20xx does not jeopardize compliance
with any requirements of any product standard the FC20xx meets (e. g. EN 54-2).