2.3 Management System Server
Please ensure that the project in the Management System Server does not reach
any of the system restrictions listed in the following table. In case of a distributed
system please refer to section Distributed System Configurations [➙ 37].
Desigo CC
Topic
System Limits
Maximum number of objects handled by the
Management System Server
150,000 (requires HW Category LS, restricted to 2
languages)
Maximum number of Installed Clients
10
Maximum number of Windows App and Web
Clients
30
Maximum
number of Flex Clients
40
Maximum number of active Web service
sessions
10 (if IIS runs on Windows 7/10)
100 (if IIS runs on Windows Server 2012
R2/2016/2019)
Maximum number of FEPs
5
Maximum number of drivers per FEP
40
Maximum number of drivers per Server. See
note below
Local: 20 (in a Server)
Total: 100 (split between the local Server and a
minimum of 2 FEPs)
Maximum number of VMS Servers connected
1
Only one Video API instance can operate with a VMS
system. Multiple Desigo CC projects running video on
the same machine are not supported. Multiple Video
API instances in parallel are not allowed
Maximum number of archived energy
datapoints in Powermanager extension
300
It does not affect the meter integrations outside of
Powermanager or non-accumulative parameters (e.g.
Voltage).
Maximum of tags exposed by the OPC Server
40,000
Maximum number of integrated OPC Servers
per OPC Client driver
20
Maximum name length of OPC tags integrated
via OPC Client driver
100
Max. number of SORIS objects per SORIS
driver
10,000
Minimum network throughput for Windows
App or Web Clients using VPN
Minimum 512 kbps up/6 Mbps down (ADSL)
Maximum Latency: 100 ms
Alarm load
(rate of new alarms)
Desigo CC has been tested for the alarm loads
defined below. Do not exceed:
Constant load of 1 alarm per second on average
10 alarms per second on average over a period of 20
minutes
50 alarms per second over a period of 20 seconds
(alarm burst)
(The test was measured with one alarm burst per
hour).
"Alarm per second” indicates the of a new
event/fault/alarm and includes the handling cycle until
it is closed later. If Operating Procedures (OPS) are
used during event handling, the maximum load is
reduced depending on the complexity of the OPS.
Maximum number of Activity logs per day