User Manual

Part B: System Dimensioning
Management System Server
2
36 | 53
Restricted
A6V10415500_en_a_42
Desigo CC
Maximum number of Event records per day
1,000,000
Maximum number of Trend records per day
4,200,000
Maximum number of reactions defined
800
Maximum number of reactions that can be
executed simultaneously
320
Graphics performance
Following results represent the time till the
background and all symbols in the graphic page are
fully rendered and updated on the client. Results on
category CL machines with HQ library symbols are:
Floor Plan with Fire 500 detectors: approx. 7 seconds
Air Handling Unit Graphic with 52 BA symbols:
approx. 2 seconds.
These results are based on the experience obtained
in a controlled lab environment. Results might be
different depending on deployment type, subsystems
used and implementation of graphics engineering.
Each driver adds approximately 25 seconds to the overall startup time on a
system installed in a LS hardware category. For hardware category definitions
refer to section Hardware Category Definitions [➙ 31].
Scope
System Limits
Comments
Recipient Users
20,000
Engineered recipient users with
recipient user devices of any
kind
Templates
200
Engineered incident and
notification templates
System Devices
2,500
Engineered devices
Service Class
Device Type
Small
Medium
Large
Max. number of running Mass Notification drivers on main Desigo
CC server (use FEP for more drivers)
5
5
5
Sign support
Adaptive display
100
200
300
Sign support
Prolite displays
100
200
300
Media display support
Media display devices
100
200
300
Audio zone support
Multi Zone Audio device
20
60
150
Audio zone support
Single Zone Audio device
20
60
150
PBX Extended (shared with Dial-
In)
Hot Line device
10
30
48
Desktop messaging support
Desktop Notification device
5,000
10,000
20,000
Hosted messaging support
Bulk Notification Email
5,000
10,000
20,000