Connections
Interfaces
Ethernet Plugs: 2 x RJ45, screened
Interface type: 10Base-T/100BASE-TX, IEEE 802.3 compatible
Bitrates: 10/100 Mbps, autosensing
Protocol: BACnet over UDP/IP
USB (2.0) Plug: Type B
Data rate: 12 Mbps
KNX Type: KNX TP1 PL-Link, galvanic isolation
Baud rate: 9.6 kbps
Bus power: 50 mA
Short-circuit proof, and protected against faulty wiring at max. AC 24 V
Wiring connections
Pluggable screw terminals Copper wire or copper stranded wire with connector sleeves
1 x 0.6 mm ø to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.6 mm ø to 1 mm
2
(22 to 18 AWG)
Copper stranded wire without connector sleeves
1 x 0.6 mm ø to 2.5 mm
2
(22 to 14 AWG) or
2 x 0.6 mm ø to 1.5 mm
2
(22 to 16 AWG)
Stripping length 6...7.5 mm (0.24...0.29 in)
Slotted screws Size 1, tightening torque 0.6 Nm (0.44 lb-ft)
Wiring lengths for signals KNX PL-Link 80 m (260 ft) with internal bus power or 300 m
(990 ft) with external power supply
Ethernet 100 m (330 ft)
Signal lines 80 m (260 ft)
For inputs AI 100 kOhm, AI NTC10K, AI NTC100K: 30 m (100 ft)
or 80 m (260 ft), if shielded.
Conformity
Ambient conditions and protection classification
Classification per IEC/EN 60730
Function of automatic control devices
Pollution degree
Overvoltage category
Type 1
2
III
Design type Device suited for use with equipment of safety classes I
and II
Degree of protection of housing to IEC EN 60529
Room automation station
With terminal cover
IP20
IP30
Climatic ambient conditions
Transport (packaged for transport) as per IEC
EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2K3
Temperature -25...70 °C (-13... 158 °F)
Air humidity 5...95% (non-condensing)
Class 3K5
Temperature -5...45 °C (23... 113 °F)/
-5...50 °C (23... 122 °F)
See Mounting
Air humidity 5...95% (non-condensing)
Mechanical ambient conditions
Transport as per IEC/EN 60721-3-2
Operation as per IEC/EN 60721-3-3
Class 2M2
Class 3M2