Example 3: DXR2x09
Use Type Signal Load
Chilled/heated ceiling - - -
6-port control ball valve GDB116.9E 0…10 V 3 VA
Condensation monitor QXA2100 DI 1 VA
Overall load 4 VA
NOTICE
Separate AC 24 V supply for field devices (V~)
A separate AC 24 V field supply is required if field devices and Triac outputs use more than
4 VA or have peak loads in excess of 6 VA.
Do not use the external field supply for the triacs. The external field supply is reserved for
field devices only, which in turn, must be controlled by an analog output (Y10...Y30).
Connecting an external supply to the triacs (V~) will destroy the room automation station.
Digital inputs
Digital inputs are not suitable for operating lighting or blinds. Use the KNK PL-Link
pushbutton.
Mounting
The room automation stations can be snapped onto standard rails or screwed onto a flat
surface.
CAUTION
Risk of overheating for failure to comply with ambient temperature
Burning and damage to the device
Ensure sufficient ventilation to comply with the permissible ambient temperature within
the panel or installation box. The temperature must be 10° C (18° F) lower outside the
installation box.
Mounting position
Ambient temperature -5...45 °C (23...113°F) Ambient temperature -5...50 °C (23...122°F)
1. Overhead
2. Wall, vertically
From top to bottom
From bottom to top
3. On a horizontal surface
Wall, horizontal
From left to right
From right to left