Desigo™ Room Automation Compact room automation stations, BACnet MS/TP, AC 24 V DXR2.M11.., DXR2.M12P.., DXR2.M12PX.., DXR2.M18.. For building with increased demands placed on functionality and flexibility in Room Automation and VAV applications.
Features Programmable The DXR2... room automation stations provide the infrastructure for system and applicationspecific functions and can be programmed. Compact series The compact build permits mounting in narrow spaces and on standardized rails, and is particularly well suited for compact panels or plants with integrated panel. Plug-in terminal blocks Plug-in terminal blocks to easily exchange room automation stations.
Functions The selected application and its parameters as well as input and output configuration determine the room automation station's functionality. A detailed description of functionality is available in the ABT (Automation Building Tool) online help. Communication ● BACnet MS/TP ● USB connection for service and commissioning, firmware download, and LAN access.
Type summary The devices are supplied without terminal covers. The terminal covers must be ordered separately. See Accessories. Order numbers: World (excluding the U.S. and Canada) Type Stock number Applications Inputs Outputs DXR2.M11-101A S55376-C112 Fan coil, radiant ceiling, radiator, 4 luminaires & 2 blinds 1 DI, 2 UI 6 Triacs, 2 AO DXR2.
Notes Safety CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. ● Observe national provisions and comply with the appropriate safety regulations. Engineering Identification Each device has a unique serial number to ensure efficient commissioning. It is provided on the adhesive barcode label. The serial number can be read directly into the engineering tool using a barcode reader.
Mounting The room automation stations can be snapped onto standard rails or screwed onto a flat surface. CAUTION Risk of overheating for failure to comply with ambient temperature Burning and damage to the device ● Ensure sufficient ventilation to comply with the permissible ambient temperature within the panel or installation box. The temperature must be 10° C (18° F) lower outside the installation box. Mounting position Ambient temperature -5...45 °C (23...113°F) Ambient temperature -5...50 °C (23...
Operation The outputs have no electricity when power fails. USB communications that does not work points to improper grounding of AC 24 V operating voltage (connection ⏊ must be grounded). Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage. ● Dispose of the device through channels provided for this purpose. ● Comply with all local and currently applicable laws and regulations.
Technical data Housing Color RAL 7035 (light-gray) Dimensions See Dimensions Weight DXR2.M11.. DXR2.M12P.. DXR2.M18.. Terminal cover Packaging ca. 330 g ca. 340 g ca. 360 g ca. 80 g ca.
Inputs The inputs are protected against incorrect wiring AC 24 V. Inputs: Overview Type Inputs DXR2.M11.. 1 DI, 2 UI DXR2.M12P.. 1 DI, 2 UI, ΔP sensor DXR2.M18.. 2 DI, 4 UI Resistance sensor, analog (inputs X...) Type Range (over range) Resolution AI 1000 Ohm *) 1 kΩ (0...1.05 kΩ) 1Ω AI 2500 Ohm *) 2.5 kΩ (0...2.625 kΩ) 2.5 Ω AI 10 kOhm *) 10 kΩ (0...10.5 kΩ) 10 Ω AI 100 kOhm *) 100 kΩ (0...105 kΩ) 100 Ω Temperature measurement, analog (inputs X...
Differential pressure sensor (inputs P1+, P1-) Connections (nipple diameter) 5.2 mm Measuring range 0...500 Pa Overload range 0...100 kPa Measuring range accuracy Zero point accuracy Resolution 4.5% 0.2 Pa 12 Bit Outputs The outputs are protected against short circuiting and incorrect wiring AC 24 V. Outputs: Overview Type Outputs DXR2.M11.. 6 Triacs, 2 AO DXR2.M12P.. 6 Triacs, 2 AO DXR2.M18.. 8 Triacs, 4 AO Analog (outputs Y10...
Connections Interfaces MS/TP Interface type: RS485 Galvanic isolation: Yes Baud rates: 9600, 19200, 38400, 57600, 115200 Protocol: BACnet over MS/TP Short-circuit proof protection against faulty wiring at max. AC 24 V USB (2.0) Plug: Type B Data rate: 12 Mbps KNX Type: KNX TP1 PL-Link, galvanic isolation Baud rate: 9.6 kbps Bus power: 50 mA Short-circuit proof, and protected against faulty wiring at max.
Standards, directives and approvals Product standard IEC/EN 60730-1 Automatic electronic controls for household and similar use Product family standard EN 50491-2, EN 50491-3, EN 50491-5 General requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS) Electromagnetic compatibility For residential, commercial, and industrial environments EU conformity (CE) EU declaration of conformance DXR2..
Pin Description Terminal 51...52 power 24 V~ Power supply AC 24 V V~ System neutral (must always be grounded at the transformer) ⏊ Switching output AC 24 V Y1...Y6 System neutral ⏊ Positioning output DC 0...10 V Y10, Y20 System neutral ⏊ Field supply AC 24 V V~ Service Service button SVC Display Operation LED RUN 61...69 Triacs 81...84 analog outputs Module Channel 11 1...6 21 1, 2 9205Z01 DXR2.M12P DXR2.M12P Pin Description 21...
9205Z03 DXR2.M18 DXR2.M18 Pin Description 21...23 MS/TP MS/TP connection 11, 12 KNX KNX connection +, - 31...41 inputs Digital input Universal input System neutral ⏊ Field supply AC 24 V for active sensors V~ Field supply DC 24 V for active sensors V+ Module Channel D1, D2 1 1, 2 X1...X4 1 5...8 11 1...8 21 1...4 , +, - USB USB interface 51...
Dimensions Without terminal cover 4,5 mm (0.18 in) 4,2 mm (0.16 in) 165 mm (6.5 in) 9205M01 59,5 mm (2.34 in) 104,5 mm (4.11 in) 35,5 mm (1.4 in) 97,6 mm (3.84 in) 6 180 mm (7.09 in) 59,5 mm (2.34 in) Siemens Smart Infrastructure 137,3 mm (5.4 in) 35,5 mm (1.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724 2424 www.siemens.com/buildingtechnologies 16 Siemens Smart Infrastructure Document ID CM1N9207en Edition 2020-10-08 © Siemens Switzerland Ltd, 2013 Technical specifications and availability subject to change without notice.