A6V11159798_en--_03 31 | 71
Central function 1st floor
Tenant A
Floor 1
Tenant B
Floor 2
Tenant C
Floor 3
Tenant D
The entire building,
across floors
AS500
Scheduler for
shading, building
occupancy
SchedSh0
Scheduler, shading,
occupancy, ground
floor
SchedSh1
Scheduler, shading,
occupancy, 2nd floor
SchedSh2
Scheduler, shading,
occupancy, 3rd floor
SchedSh3
Scheduler, shading,
occupancy, 4th floor
AS500
Scheduler for
shading, system
operation
SchedSh6
Scheduler, shading
system operation.
Ground floor
SchedSh7
Scheduler, shading
system operation.
2nd floor
SchedSh8
Scheduler, shading
system operation.
3rd floor
SchedSh9
Scheduler, shading
system operation.
4th floor
Central emergency
shading (overall)
CenEmgShd
Central protection
function shading
CenPrtShd
Central service
function
Blinds
CenSrvShd_EG CenSrvShd_1OG CenSrvShd_2OG CenSrvShd_3OG
Central facade
shading west
CenFcdShd_W
Central facade
shading south
CenFcdShd_S
Central facade
shading east
CenFcdShd_E
Hot water supply
chain
SplyHw
Supply chain chilled
water
SplyChw
Recommendation: Network components
Siemens SCALANCE XB005 - as the edge switch for cabling PXC and Desigo room automation stations.
Siemens SCALANCE XB005 - At the distribution level in the riser zones.
Siemens SCALANCE XB205 - At the distribution level with port mirroring for diagnostics.
IT security and IT basic protection
The elements of infrastructure, IT systems, networks, and applications must be discussed under the
aspects of security and appropriate measures need to be developed. Customer, domestic, or industry
guidelines and directives must be observed under all circumstances.
For additional details, see
IT security on installations with Desigo
(CM110663) and
Practical Guide on IP
Networks in Building Automation and Control Systems
(CM110668).
Summary
The following tables show how to depict all devices and network components in a small project.
Plant category Number of IP devices
PXC primary plants 5
PXC3/DXR2 individual room control & central functions 121
PXC00-E.D system controller, building scope 1
Reserves 5% 6
Amount 133