User Manual

BACnet/IP networks
Designing BACnet/IP networks
4
38 | 71 A6V11159798_en--_03
Desigo PXC00-E.D for monitoring Desigo room automation stations.
Desigo DXR2.E18/PXC3.E.. for central functions within the floor scope.
Desigo DXR2.E../PXC3.E.. for room and room segments / HVAC, lighting, and blinds.
You can operate with cascading group master functions if lighting and blinds exceed a maximum of 500
commandable group members. This could, for example, be used for emergency control of blinds actuators
over multiple facades over lighting over multiple floors.
Notes on project implementation
In the project example above was generously planned (since it is a midsized to large project) and one
PXC00-E.D was assigned to each floor scope as well. It assumes monitoring of Desigo room automation
stations. The PXC00-E.D in the building scope is used for scheduling and superposed functions for various
floors as well as central functions for room operating mode, lighting, and blinds.
Depending on building design, air handling may be decentralized on various floors. A PXC100-E.D each is
used in the floor scope to this end. It takes over scheduling and superposed functions for the floor / floor
scope. The PXC00-E.D monitoring unit is used in the building scope to monitor Desigo room automation
stations.
Planning and implementation of central functions
Central function Ground floor Floor 1 Floor 2 Floor 3 Entire building
Hardware AS1001 AS2001 AS3001 AS4001 AS5001ZF
Central weather
station
CenWthStn
Central setpoint
generation via
seasonal
compensation for
North, East, South,
West
CenSsnN
CenSsnE
CenSsnS
CenSsnW
Central operating
mode determination
CenOp_EG CenOp_1OG CenOp_2OG CenOp_3OG
AS501SC
Scheduler for room
operating mode
SchedOp0
Scheduler, room
operating mode
ground floor
SchedOp1
Scheduler, room
operating mode 2nd
floor
SchedOp2
Scheduler, room
operating mode 3rd
floor
SchedOp3
Scheduler, room
operating mode 4th
floor
Central operation
lighting
CenOpLgt_EG CenOpLgt_1OG CenOpLgt_2OG CenOpLgt_3OG
AS501SC
Scheduler for
lighting, building
occupancy
SchedLg0
Scheduler, lighting
occupancy, ground
floor
SchedLg1
Scheduler, lighting,
building occupancy,
2nd floor
SchedLg2
Scheduler, lighting,
building occupancy,
3rd floor
SchedLg3
Scheduler, lighting,
building occupancy,
4th floor
AS501SC
Scheduler for
lighting, system
operation
SchedLg6
Scheduler, lighting
system operation
Ground Floor.
SchedLg7
Scheduler, lighting
system operation
2nd floor.
SchedLg8
Scheduler, lighting
system operation
3rd floor.
SchedLg9
Scheduler, lighting
system operation
4th floor.
Central emergency
function lighting
CenEmgLgt_EG CenEmgLgt_1OG CenEmgLgt_2OG CenEmgLgt_2OG
Central emergency
lighting (overall)
CenEmgLgt
Zentrale Bedienung
Jalousie
CenOpShd_EG CenOpShd_1OG CenOpShd_2OG CenOpShd_3OG
AS501SC
Scheduler for
shading, building
occupancy
SchedSh0
Scheduler, shading,
occupancy, ground
floor
SchedSh1
Scheduler, shading,
occupancy, 2nd floor
SchedSh2
Scheduler, shading,
occupancy, 3rd floor
SchedSh3
Scheduler, shading,
occupancy, 4th floor