User Manual

BACnet/IP networks
Designing BACnet/IP networks
4
42 | 71 A6V11159798_en--_03
Description Ground
floor
DXR2
2nd floor
DXR2
3rd floor
DXR2
4th floor
DXR2
BA Mgmt
DXR2
Primary
plants
System
level
Refrigerati
on
machines
BACnet
3rd
Sinteso
FS20
BMA
Reserve IP
addresses
149 149 149 149 247
IP address
range for
DXR2
from…
192.168.11.
1
192.168.12.
1
192.168.13.
1
192.168.14.
1
192.168.15.
1
IP address
range for
DXR2 ...to
192.168.11.
200
192.168.12.
200
192.168.13.
200
192.168.14.
200
192.168.15.
50
PXC00-E.D
monitoring,
floor scope
192.168.11.
201
192.168.12.
201
192.168.13.
201
192.168.14.
201
Central
functions,
floor scope
192.168.11.
1
192.168.12.
1
192.168.13.
1
192.168.14.
1
Central
functions,
superposed,
building
scope
192.168.15.
1…2
PXG3.M,
BBMD in
the floor
scope
192.168.11.
250
192.168.12.
250
192.168.13.
250
192.168.14.
250
PXG3.M,
central
BBMD in
the building
scope
192.168.15.
250
PXC00-E.D
scheduler
for floor
scope
192.168.15.
51
Number of
PXC, FS20,
BACnet3rd
3 1 2 10
Reserve IP
addresses
251 253 248 240
IP address
range
from…
192.168.16.
1
192.168.17.
1
192.168.20.
1
192.168.21.
1
IP address
range ...to
192.168.16.
249
192.168.17.
249
192.168.20.
249
192.168.21.
249