User Manual

BACnet networks with MS/TP trunks
Application examples
5
A6V11159798_en--_03 61 | 71
Central function Ground floor Floor 1 Floor 2 Floor 3 Entire building
AS501SC
Scheduler for room
operating mode
SchedOp0
Scheduler, room
operating mode
ground floor
SchedOp1
Scheduler, room
operating mode 2nd
floor
SchedOp2
Scheduler, room
operating mode 3rd
floor
SchedOp3
Scheduler, room
operating mode 4th
floor
Central operation
lighting
CenOpLgt_EG CenOpLgt_1OG CenOpLgt_2OG CenOpLgt_3OG
AS501SC
Scheduler for
lighting, building
occupancy
SchedLg0
Scheduler, lighting
occupancy, ground
floor
SchedLg1
Scheduler, lighting,
building occupancy,
2nd floor
SchedLg2
Scheduler, lighting,
building occupancy,
3rd floor
SchedLg3
Scheduler, lighting,
building occupancy,
4th floor
AS501SC
Scheduler for
lighting, system
operation
SchedLg6
Scheduler, lighting
system operation
Ground Floor.
SchedLg7
Scheduler, lighting
system operation
2nd floor.
SchedLg8
Scheduler, lighting
system operation
3rd floor.
SchedLg9
Scheduler, lighting
system operation
4th floor.
Central emergency
function lighting
CenEmgLgt_EG CenEmgLgt_1OG CenEmgLgt_2OG CenEmgLgt_2OG
Central emergency
lighting (overall)
CenEmgLgt
Central blinds
operation
CenOpShd_EG CenOpShd_1OG CenOpShd_2OG CenOpShd_3OG
AS501SC
Scheduler for blinds,
building occupancy
SchedSh0
Scheduler, blinds,
occupancy, ground
floor
SchedSh1
Scheduler, blinds,
occupancy, 1st floor
SchedSh2
Scheduler, blinds,
occupancy, 2nd floor
SchedSh3
Scheduler, blinds,
occupancy, 3rd floor
AS501SC
Scheduler for blinds,
system operation
SchedSh6
Scheduler, shading
system operation
ground floor.
SchedSh7
Scheduler, shading
system operation
1st floor.
SchedSh8
Scheduler, shading
system operation
2nd floor.
SchedSh9
Scheduler, shading
system operation
3rd floor.
Central emergency
shading (overall)
CenEmgShd
Central protection
function shading
CenPrtShd
Central service
function shading
CenSrvShd_EG CenSrvShd_1OG CenSrvShd_2OG CenSrvShd_3OG
Central facade
shading west
CenFcdShd_W
Central facade
shading south
CenFcdShd_S
Central facade
shading east
CenFcdShd_E
Hot water supply
chain
SplyHw SplyHw SplyHw SplyHw SplyHw (Total)
Supply chain chilled
water
SplyChw SplyChw SplyChw SplyChw SplyChw (Total)
Supply chain
ventilation
SplyAir SplyAir SplyAir SplyAir SplyAir (Total)
Recommendation: Network components
Siemens SCALANCE XB005 - as the edge switch for cabling PXC and Desigo room automation stations.
Siemens SCALANCE XB205 - At the distribution level in the riser zones for setting up VLANs and port
mirroring for diagnostics.
Siemens SCALANCE XM405 - As core switch for possible IP routing.
Siemens SCALANCE switches from the product family X-200 or X-400 support SNMP and can be monitored
on Desigo CC.