Diagnostics and troubleshooting in BACnet networks with MS/TP trunks
5
A6V11159798_en--_03 67 | 71
Faults Possible causes & troubleshooting
Communication is slow. A master device normally holds the token for only a few milliseconds, with the
forwarding to the next device taking up to 250 ms. In other words, a high
number of devices causes a high cycle which requires a very conservative
(long) timeout value. You must configure the following timeouts if MS/TP
devices participate in the communication:
APDU timeout: 6000 ms
APDU segment timeout: 5000 ms
Max Info frames: 50
Operation on the Desigo CC management platform requires, where there are
lots of BACnet MS/TP devices, reading the functions sequentially by
discipline. This requires training course and operator instructions.
Communication no longer restarts after a power
outage or communication no longer starts after
a power outage on the BACnet/IP router.
Communication – Data traffic is too high or way too high. In other words,
reduce or cease the following:
Room segment communication
No lighting or blinds application
Max. one Desigo CC management platform
Max. 5 trends per room
Max. 3 alarms per room
No central functions for gathering, i.e. for the hot water supply chain,
chilled water, air
BACnet networks PXG3.M runs automatic network checks, and indicates errors with an
illuminated Info-LED.
PXG3.M operates on large projects as BBMD. These devices must have a
fixed IP address and not DHCP.
Only one PXG3.M with BBMD functionality permitted per BACnet network.