Faults Possible causes & troubleshooting
Communication is slow. ● A master device normally holds the token for only a few milliseconds, with the
forwarding to the next device taking up to 250 ms. In other words, a high
number of devices causes a high cycle which requires a very conservative
(long) timeout value. You must configure the following timeouts if MS/TP
devices participate in the communication:
– APDU timeout: 6000 ms
– APDU segment timeout: 5000 ms
– Max Info frames: 50
● Operation on the Desigo CC management platform requires, where there are
lots of BACnet MS/TP devices, reading the functions sequentially by
discipline. This requires training course and operator instructions.
Communication no longer restarts after a power
outage or communication no longer starts after
a power outage on the BACnet/IP router.
● Communication – Data traffic is too high or way too high. In other words,
reduce or cease the following:
– Room segment communication
– No lighting or blinds application
– Max. one Desigo CC management platform
– Max. 5 trends per room
– Max. 3 alarms per room
– No central functions for gathering, i.e. for the hot water supply chain,
chilled water, air
BACnet networks ● PXG3.M runs automatic network checks, and indicates errors with an
illuminated Info-LED.
● PXG3.M operates on large projects as BBMD. These devices must have a
fixed IP address and not DHCP.
● Only one PXG3.M with BBMD functionality permitted per BACnet network.
Have you considered notes from technical