User Manual

106/118
Siemens TX-I/O Engineering and installation guide CM110562en_13
Building Technologies Principles of electrical design 2019-05-15
Overvoltage protection devices can falsify the measured value of analog inputs.
Example: Phoenix type PT 1X2-12DC-ST/28 56 02 9 has an internal protective impe-
dance which causes a measuring error of +1K, but only for LG-Ni 1000 sensors.
Pt 1000 sensors: Measured value error due to line resistance
2
1
0
100 200 300
1 mm
²
F [K]
L [m]
1,5 mm
²
2,5 mm
²
10762d035
0,6 mm Ø
-0,26
Formula: F =
3.9
1
A57
L2
Key
A Cable cross-section in mm
2
F Measured temperature error in K
L Cable length in m
The 4-wire circuit serves to eliminate the error due to line resistance.
The measuring value function has no predefined line resistance.
in addition, the very small pulsed sensor current minimizes the internal heat
dissipation in the Pt100 sensor.
T1 sensors: Measured value error due to line resistance:
0.2
0
-0.1 100 200
300
1 mm
²
L [m]
0.4
0.6
0.8
F [K]
10762d055
1,5 mm
²
2,5 mm
²
0,6 mm Ø
1.0
Formula: F =
10
1
A57
L2
A Cable cross-section in mm
2
F Measured temperature error in K
L Cable length in m
Measured value error
LG-Ni 1000
b)
Measured value error
due to explosion
protection devices
Measured value error
Pt 1000 sensor
Measured value
error
Pt 100
sensor
(4-wire)
Measured value er
ror
T1
Key