Siemens TX-I/O Engineering and installation guide CM110562en_13
Building Technologies Principles of electrical design 2019-05-15
10.12.5 Technical data for the analog inputs
Compensation of the line
resistance
1 Ohm, calibrated in the module,
(except for Pt100_4, P100, NTC10K and NTC100K)
Signaltyp Range
(Under / over range)
5)
Resolution
island bus
3)
Resolution
P-Bus-BIM
3)
Resolution
PROFINET
BIM 3)
Sensor
current
(cyclic
polling)
Temperature AI Pt100 4 Wire
-50...400 (600) °C 1) 2)
(-52.5...610°C)
20 mK 86 mK 20 mK
(Climatic)
100 mK
(Standard)
2.1 mA
Resistance AI Pt100 0...250 Ohm 2)
(0...265 Ohm)
10 mOhm 33 mOhm
-- 2.1 mA
Resistance AI 250 Ohm
(2-Draht)
0...250 Ohm 2)
(0...265 Ohm)
10 mOhm 33 mOhm
100mOhm 2.1 mA
Temperature AI PT1K 375
-50…150 (180) °C 1) 6)
(-52.5 ...185.0 °C)
10 mK
10mK 1.54 mA
Temperature AI PT1K 385
-50...400 (600) °C 1)
(-52.5...610°C)
20 mK
100 mK
1.96 mA
Temperature AI Ni1000
(LG-Ni 1000)
-50...150°C
(-52.5...155.0 °C)
10 mK
50 mK
10 mK
1.54 mA
Temp. AI Ni1000 extended
(LG-Ni 1000)
-50…150 (180) °C 1)
(-52.5...185.0 °C)
10 mK
10mK
1.54 mA
Resistance AI Pt1000 0...2500 Ohm
(0...2650 Ohm)
100 mOhm 333 mOhm -- 1.96 mA
Resistance AI 2500 Ohm 0...2500 Ohm
(0...2650 Ohm)
100 mOhm 100 mOhm 1.96 mA
Temperatuer AI T1 (PTC)
-50...130 (150) °C 1)
(-52.5...155.0 °C)
10 mK 50 mK 10 mK
1.26 mA
Temperature AI NTC10K
(-40...115 °C) 1)
(-52.5...155°C)
10 mK (25°C) 10 mK
0.14 mA
Temperature AI NTC100K
(-40 ...125 °C) 1)
(-52.5...155°C)
10 mK (25°C) 10 mK
0.14 mA
Voltage measuring AI 0-10V 0 ... 10 V 4)
(-1.5...11.5 V)
1 mV 3.125 mV 1 mV
Current measuring AI 4-20mA 4 ... 20 mA
(1.6...22.4 mA)
1 µA 5 µA 1 µA
AI 0-20mA 0 ... 20 mA
(-3.0...23 mA)
(25 mA see CM10563)
1 µA 6.25 µA 1 µA
Load resistance: 490 / 440 Ohms, pulsed (cyclic polling of the I/O points)
1) (extended range) only with reduced hum injection (see below)
2) In direct island bus integration, Pt100_4 and P100 are connected with 4 wires, R250
is connected with 2 wires.
The P-Bus BIM integration in V4 and later supports P100 4-wire and R250 2-wire,
but R250 must be connected to 4 terminals with jumpers.
Connection diagrams see data sheet N8176.
The resolution with island bus is significantly better than with island bus BIM / P-Bus.
3) This section describes the measured resolution. (Desigo: It is different from the
transmitted resolution that the bus delivers into the AI block and that is transformed
by [Slpe] and [Icpt], see section 10.12.2).