Fuses to protect
AC 24 V operating
voltage
Important
Transformers, secondary winding: based on the
effective
load of all connected devices in accordance with the
transformer sizing
:
The AC 24 V conductor (system potential) must always be
fused
Where specified, an additional fuse must be provided for the
reference conductor (system neutral).
The 10 A fine-wire fuses fitted to the power supply units to
protect the I/O island are not a substitute for the load-
dependent back-up fuse.
Refer to Section10.9.
The introduction of hazardous voltages into the low voltage circuits of the system (e.g.
due to faulty wiring or to parasitic voltages in the TX-I/O modules) represents an
immediate danger to personal safety and may cause irreparable damage to the building
automation and control system.
Adhere to local regulations on lighting protection and equipotential bonding.
Overvoltage protection devices can falsify the measured value of analog inputs.
Example: Phoenix type PT 1X2-12DC-ST/28 56 02 9 has an internal protective impe-
dance which causes a measuring error of +1K, but only for LG-Ni 1000 sensors.
Adhere to local regulations on Explosion protection.
Explosion protection devices can falsify the measured value of analog inputs.
Example: Pepperl & Fuchs type CFD2-RR-Ex19 causes considerable measuring
errors for resistance values of <30 ohms. Resistances >30 ohms are measured
correctly.