6.4.3 Wiring island bus expansion
Wiring material See Section 10.6
Maximum wire length See Section 10.6
Cabling the bus cable Low-voltage wiring and cabled next wiring mains voltage, must have the same
isolation strength as is used for the mains voltage.
We recommend separating low-voltage wiring from mains voltage for reasons of
electro-magnetic compatibility. Recommended minimum distance: 150 mm.
Bus topology Line topology only is allowed
ONE island bus expan-
sion module only per
sub-island
Cascading (more than one island bus expansion module per sub-island) is not
permitted.
System ground (
) The island bus expansion operates without system ground ().
The system ground () must be connected when a remote sub-island is powered
by the local sub-island. The wire must be routed together with the cable for the
island bus expansion.