6.5 Wiring examples
6.5.1 Principles
AC 24 V is always connected in a "star" configuration (from terminal block K)
For longer distances (typically between two control panels), the cables for bus and
AC 24 V / ⊥ MUST be tied together.
For shorter distances, also inside the control panel, we recommend this as well.
Admissible cable lengths see Sections 10.4 and 10.5.
T
K
10762z058
Transformer
Terminal block for the distribution of AC 24 V
Bus cable for CS and CD
Cable for AC 24 V and system neutral ⊥
Cable V
for field supply and system neutral ⊥
Cable for system neutral ⊥
Tie cables together *)
Automation station + power supply module
P-BusBus interface module with built-in power supply
PROFINET BIM plus power supply module
Supply module (TXS1.12F10)
Bus connection module (TXS1.EF10)
Row of I/O modules with island bus
*) Tie cables together to avoid loops (inductive disturbances),
BUT do not route the ⊥ conductor in the same cable (capacitive disturbances).
The connections between the terminals and bus cables are as follows: