User Manual

45/118
Siemens TX-I/O Engineering and installation guide CM110562en_13
Building Technologies Wiring 2019-05-15
6.5 Wiring examples
6.5.1 Principles
AC 24 V is always connected in a "star" configuration (from terminal block K)
For longer distances (typically between two control panels), the cables for bus and
AC 24 V / MUST be tied together.
For shorter distances, also inside the control panel, we recommend this as well.
Admissible cable lengths see Sections 10.4 and 10.5.
T
K
10762z058
Transformer
Terminal block for the distribution of AC 24 V
Bus cable for CS and CD
Cable for AC 24 V and system neutral
Cable V
for field supply and system neutral
Cable for system neutral
Tie cables together *)
Automation station + power supply module
P-BusBus interface module with built-in power supply
PROFINET BIM plus power supply module
Supply module (TXS1.12F10)
Bus connection module (TXS1.EF10)
Row of I/O modules with island bus
*) Tie cables together to avoid loops (inductive disturbances),
BUT do not route the conductor in the same cable (capacitive disturbances).
The connections between the terminals and bus cables are as follows:
TXS1.12F10 power supply module TXS1.EF10 bus connection module
24V~
CD
CS
CD
CS
3 4 5 6
CS CD
1 2
24V~
CS CD
10562A012
10A
V~
CD
CS
CD
CS
3 4 5 6
CS CD
1 2
CS CD
10562A013
10A
V~
Note
Key
Internal circuit