User Manual

46/118
Siemens TX-I/O Engineering and installation guide CM110562en_13
Building Technologies Wiring 2019-05-15
6.5.2 Example: 1 transformer, 1 or 2 control panels
10562z048
T
K
K
6.5.3 Example: 2 transformers, 1 or 2 control panels
10562z049
T
K
T
K
System neutral of the two transformers must be connected as close as possible to
the transformers.
6.5.4 Example: New power supply (module supply or AC 24 V)
10562z050
T1
K
A new provision is required in the following cases (for details refer to Section 10.3):
When the admissible supply current of 1.2 A in the module supply is "used up"
by the I/O modules and the field devices: a new power supply module is required
(operating in parallel with the first one).
When the admissible supply current of 6 A in the field supply is "used up" by the
field devices: a new power supply module or bus connection module is required.
New circuit with separate fuse.
The CS and CD conductors of the power supply modules and bus connection
modules are connected internally, so that these are available to the whole I/O row.
The field supply (AC 24 V
) has no bus connector on the left side, so that only the
I/O modules to the right are supplied.
Note
Notes