Siemens TX-I/O Engineering and installation guide CM110562en_13
Building Technologies Principles of electrical design 2019-05-15
10.5.2.4 Multiple supplies
If currents higher than 1.2 A must flow out of an I/O row, a multiple supply is required.
If two or more supplies together deliver current to an I/O row other than their own (be it
local or remote), these supplies must themselves be placed in different I/O rows.
They must be connected by a short cable via the screw terminals.
10562z111
TXS1.12F10
I > 1.2 A
TXS1.EF10
TXS1.12F10
V2.37: TXB1.P-BUS
V4: AS + Supply
TXS1.EF10
I < 1.2 A
V2.37: TXB1.P-BUS
V4: AS + Supply
Recommended
Admissible
when I < 1.2 A