User Manual

94/118
Siemens TX-I/O Engineering and installation guide CM110562en_13
Building Technologies Principles of electrical design 2019-05-15
10.6.6 Wiring examples for island bus expansion
Wiring of the island bus expansion can be executed in different ways, depending on
the earthing kind of the system (PELV, SELV)
the cables used (Cat 5, RS-485, RG-62).
Admissible cable types are described in 10.6.4.
Admissible cable lengths see above, rule 19.
When choosing a protection system (PELV, SELV), local safety regulations must be
observed.
A simple and effective installation is achieved with PELV earthing and CAT 5 (AWG24)
cable.
Key
Earthing and installation examples contain the following elements:
Automation station with island bus connector + power supply module TXS1.12F10
Bus Interface Module with built-in power supply TXB1.P-BUS
PROFINET BIM TXB1.PROFINET + power supply module TXS1.12F10
Power supply module TXS1.12F10
Bus connection module TXS1.EF10
Island bus expansion module TXA1.IBE
TX-I/O module TXM1....
Cable island bus
Cable island bus expansion
Earthing of the screens (
, all examples):
When you expect medium or high EMC disturbance, we recommend earthing of the
screens (on both ends) as described on page 50.
Earthing of field devices (not shown in the examples):
Earthing (e.g. external sensor power) should be avoided.
The following illustrations show wiring examples for different earthing kinds (PELV,
PELV) and different cables.
Notes on earthing